Voltage Drop & Wire Size Calculator

Voltage drop in a cable run for DC, single-phase or three-phase AC, copper or aluminium, mm² or AWG wire sizes, with the voltage at the load, power lost and the smallest wire size that keeps the drop within a limit

e.g. 230 V (Europe), 120 V (US), 400 V three-phase, 12 V DC

Distance from the supply to the load, not the total wire length

20 °C at room temperature; cables under full load often run at 70–90 °C, which raises the resistance

Common limits are 3% for a final circuit and 5% in total

This calculates voltage drop only. A wire must also be rated for the current it carries (its ampacity), which depends on insulation, how it's installed and the surrounding temperature, and is set by your local electrical code. Mains wiring should be done or checked by a qualified electrician.

How voltage drop is calculated

Every wire has some resistance, so part of the voltage is lost along the cable as heat. The drop grows with current and length and shrinks with a thicker wire. In DC and single-phase circuits the current flows out and back, so the length counts twice; in a balanced three-phase circuit the factor is √3.

ΔV = k × L × I × ρ ÷ A (k = 2 for DC / single-phase, √3 for three-phase)

L is the one-way length in metres, I the current in amps, ρ the resistivity of the conductor (copper 0.0172, aluminium 0.0282 Ω·mm²/m at 20 °C, rising about 0.4% per °C) and A the cross-section in mm². AWG (American Wire Gauge) sizes are converted to mm²; a smaller AWG number is a thicker wire.

The formula ignores cable reactance and assumes a power factor of 1, which is accurate for small and medium cables; for very large cables or motor loads the real drop can be somewhat higher.